8-2

Serial Communications

Control Enable

Per factory programming, “stop” is the only control command active
on the SMC Dialog Plus controller when the SCANport is utilized.
To enable motor control from a programmable logic controller
through a communication module, follow the programming procedure
below.

Zero and 4 are the only valid settings.

Note: If a communication module is disconnected from the SMC

Dialog Plus controller while control is enabled (Logic Mask
= 4), a Comm Fault will occur.

Description

Action

Display

1.

Press any key to access
the Choose Mode
function.

2.

Scroll with the Up/Down
keys until the Program
option appears.

3.

Press the Enter key to
access the Program
option.

4.

Scroll with the Up/Down
keys to the Linear List
option.

5.

Press the Enter key to
access the Linear List
programming group.

6.

Scroll with the Up/Down
keys to parameter number
85 - Logic Mask.

7.

Press the Select key to
move the cursor to the
second line to modify the
parameter.

8.

Press the Up key until the
value 4 appears.

9.

Press the Enter key to
accept the new setting.

STOPPED
0.0 AMPS

CHOOSE MODE
_ _ _ _ _

or

CHOOSE MODE
PROGRAM

PROGRAM
_ _ _ _ _

or

PROGRAM
LINEAR LIST

VOLTS PHASE A–B
0 VOLTS

1

or

LOGIC MASK
0

85

LOGIC MASK
0

85

LOGIC MASK
4

85

LOGIC MASK
4

85