Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 153

Advertising
background image

10-4

Troubleshooting

Table 10.B Motor Will Not Start — No Output Voltage to the Motor

Table 10.C Motor Rotates (but does not accelerate to full speed)

Table 10.D Motor Stops While Running

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 10.A
addressing fault
conditions

Display is blank

Control voltage is
absent

Failed control module

Check control wiring and
correct if necessary

Replace control module

Stopped

0.0 Amps

Pilot devices

SMC Enable input is
open at terminal 13

Terminal 15 is open on
Soft Stop, Pump
Control, and SMB

Start-Stop control has
not been enabled for
the human interface
module

Control voltage

Failed control module

Check wiring

Check wiring

Check wiring

Follow the instructions on
pages 2-13 and 2-14 to
enable control capability

Check control voltage

Replace control module

Starting

Two or three power
phases are missing

Check power system

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 10.A
addressing fault
conditions

Starting

Mechanical problems

Inadequate Current
Limit setting

Failed control module

Check for binding or
external loading and
correct

Check motor

Adjust the Current Limit
Level to a higher setting

Replace control module

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 10.A
addressing fault
conditions

Display is blank

Control voltage is
absent

Failed control module

Check control wiring and
correct if necessary

Replace control module

Stopped

0.0 Amps

Pilot devices

Failed control module

Check control wiring and
correct if necessary

Replace control module

Starting

Two or three power
phases are missing

Failed control module

Check power system

Replace control module

Advertising