Options

7-3

Programming Parameters

The following table provides the option-specific parameters that are
provided with each control option. These parameters are in addition
to those already discussed in the Basic Setup, Advanced Setup,
Metering, and Calibration groups. Diagrams supporting the options
described below are shown later in this chapter.

Option

Parameter

Range

Soft Stop

SMC Option

This parameter identifies the type of
control present and is not user
programmable.

Soft Stop

Soft Stop Time

Allows the user to set the time
period for the soft stopping function.

0–60 seconds

Pump Control

SMC Option

This parameter identifies the type of
control present and is not user
programmable.

Pump Control

Pump Stop Time

Allows the user to set the time
period for the pump stopping
function.

0–120 seconds

Starting Mode

Allows the user to program the SMC
Dialog Plus controller for the type of
starting that best fits the application.

Pump Start, Soft Start,
Current Limit Start

Preset Slow

Speed

SMC Option

This parameter identifies the type of
control present and is not user
programmable.

Preset Slow

Slow Speed Select

Allows the user to program the slow
speed that best fits the application.

Low: 7% – forward,
10% – reverse
High: 15% – forward,
20% – reverse

Slow Speed Direction

This parameter programs the slow
speed motor rotational direction.

Forward, Reverse

Slow Accel Current

Allows the user to program the
required current to accelerate the
motor to slow speed operation.

0–450% of full load
current

Slow Running Current

Allows the user to program the
required current to operate the
motor at the slow speed setting.

0–450% of full load
current