Calibration, Chapter, Overview – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 79: Motor data entry

Advertising
background image

Chapter

5

Calibration

Overview

The Calibrate programming group allows the user to set parameters to
calibrate the controller to the connected motor. It is important to
correctly input the data to achieve the best performance from your
controller.

Motor Data Entry

In the Program mode, enter the correct values into the Calibrate
group:

Refer to the SMC Dialog Plus controller nameplate for maximum ratings. Exceeding these could
result in damage to the controller.

The controller’s programming system will not allow both HP and kW to be programmed.

!

ATTENTION: For overload protection, it is critical
that the data be entered as it appears on the motor
nameplate.

Parameter

Option

Display

Overload Class

The factory default setting disables
overload protection. To enable it,
enter the desired trip class in this
parameter. See pages 1-5 and 1-7 for
further details and trip curves.

Off, 10, 15, 20, 30

Overload Reset

Allows the user to select either a
manual or auto reset after an overload
fault.

Manual, Auto

Motor HP Rating

①②

Enter the value from the motor’s
nameplate.

0.0–6,553.5 HP

Motor kW Rating

①②

Enter the value from the motor’s
nameplate.

0.0–6,553.5 kW

Line Voltage

Enter the system voltage in this
parameter. This must be done to
ensure optimum motor performance
and correct operation of undervoltage
and overvoltage protection.

1–9,999V

Motor FLC

Enter the value from the motor’s
nameplate.

1.0–999.9A

Service Factor

Enter the value from the motor’s
nameplate.

0.01–1.99

OVERLOAD CLASS
_____

OVERLOAD RESET
MANUAL

MOTOR HP RATING
#### HP

MOTOR KW RATING
#### KW

LINE VOLTAGE
#### VOLTS

MOTOR FLC
###.# AMPS

SERVICE FACTOR
#.##

Advertising