I/o addressing – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 128

Advertising
background image

Serial Communications

8-19

1203-GD1 Communication Module Switch Settings

The following information is provided to explain the required 1203-
GD1 communication module switch settings for this example. Refer
to the 1203-GD1 manuals for further details related to the switch
settings.

Example Information

This configuration requires a 1/4 rack size allocation.

The SMC Dialog Plus controller does not support Datalinks.

Switch Settings

I/O Addressing

The 1203-GD1 communication module uses 1-slot addressing. Based
on the module switch settings as described above, the discrete I/O can
be mapped to the PLC I/O Image as shown below.

Description

Switch Setting

SMC Rack Address:

02

SW1: Switches 1 & 2 (Not Used),
Switches 3-6 & 8 (On), Switch 7 (Off)

Starting Group Address:

0

SW2: Switches 1 & 2 (On)

Last Rack:

No

SW2: Switch 3 (Off)

Hold Last State:

Yes

SW2: Switch 4 (On)

Fault on Comm Loss:

Yes

SW2: Switch 5 (On)

Fault Controller:

No

SW2: Switch 6 (Off)

R I/O Baud Rate:

115k

SW2: Switch 7 (On), Switch 8 (Off)

Block Transfer:

Yes

SW3: Switch 1 (On)

Logic Cmd/Status:

Yes

SW3: Switch 2 (On)

Reference/Feedback:

No

SW3: Switch 3 (Off)

Datalinks:

No

①②

SW3: Switch 4-8 (Off)

SW

1

8

7 6

5 4

3

2

1

Not Used
Not Used
On
On
On

On

Off
On

SW

2

8

7 6

5 4

3

2

1

Starting Module Group (0)
Starting Module Group (0)
Last Rack Setting (Off)
Hold Last State (On)
Fault on Comm Loss (On)

Fault Controller (Off)

R I/O Baud Rate (115k)
R I/O Baud Rate (115k)

SW

3

8

7 6

5 4

3

2

1

Block Transfer On
Logic Cmd/Sts On
Reference/Fdbk Off
Datalink A Off
Datalink B Off

Datalink C Off

Datalink D Off
Truncate Last Datalink Off

PLC I/O Group Number

Output Image

Input Image

0

Block Transfer

Block Transfer

1

Logic Command

Logic Status

Advertising