Converter modules (cont.), Electromagnetic compatibility (emc) – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 44

Advertising
background image

2-18

Installation

Converter Modules (cont.)

For applications in which the motor’s full load current rating is
greater than 360A, three additional current transformers with 5A
secondaries are required. The figure below illustrates the connection
of the current transformers to the converter module.

Figure 2.10 Current Transformer Connection to Converter Module

The current transformer (CT) ration must be programmed in the calibration group for proper current
measurement scaling. See page 5-2 for instructions on programming this parameter.

Another current transformer connects L2 and T2, and another connects L3 and T3.

The converter module, Cat No. 825-MCM20, must be used in these applications.

Electromagnetic
Compatibility (EMC)

The following guidelines are provided for EMC installation
compliance.

Enclosure

Install the product in a grounded metal enclosure.

Grounding

Connect a grounding conductor to the screw or terminal provided as
standard on each controller. Refer to Figure 2.1 through Figure 2.5
for grounding provision location.

Current Transformer ➀➁

L1

L3

T1 T3

L2

T2

Converter Module ➂

!

.

ATTENTION: This product has been designed for
Class A equipment. Use of the product in domestic
environments may cause radio interference, in which
case, the installer may need to employ additional
mitigation methods.

Advertising