G file configuration, I/o addressing – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 116

Advertising
background image

Serial Communications

8-7

G File Configuration

The SLC system uses G files to configure the R I/O link. G files are
configured through the SLC programming software. The
configuration is based on the devices connected to the R I/O link. For
this example, the following G file configuration map for the scanner’s
I/O image file of the SMC Dialog Plus controller applies.

Words 3 and 4 do not require configuration since the communication module does not support
Complimentary I/O.

I/O Addressing

The 1203-GD1 communication module uses 1-slot addressing. Based
on the module switch settings as described above, the discrete I/O can
be mapped to the PLC I/O Image as shown below.

SLC I/O Image Table Map

The output image word that maps to the Reference word (O: 1.17, in this example) must have the
value 0 to insure proper SMC Dialog Plus controller operation.

Addressing Format

Address

15

Data

0

Description

G1:0
G1:1
G1:2

xxxx
0000
0000

xxxx
0001
0001

xxxx
0000
0000

xxxx
0000
0000

Word 0 cannot be edited
Logical device address (rack 2, start group 0)
Logical image size (1/4 rack)

SLC I/O Group Number

Output Image

Input Image

0

Logic Command

Logic Status

1

Reference

Feedback

I for input or O for output

Slot number

Word number

Input or output number
(bit identifier: 0–15)

I : 1 0/12

Advertising