B-4

Parameter Information

Table B.1 (cont.) Parameter List

Read-only capability.

The scale factor is 100 when Motor FLC, parameter 70, has a programmed value of up to 10.0 Amps; above 10.0 Amps, the scale factor is 10.

Group

Parameter

Description

Parameter

Number

Display

Units

Scale

Factor

Minimum

Maximum

Default
Setting

User

Setting

Calibrate

Overload

Class

36

Off, 10, 15, 20, and 30

Off

Overload

Reset

88

Manual-Auto

Manual

Motor HP

Rating

79

HP

10

0.0

6,553.5

0.0

Motor kW

Rating

80

kW

10

0.0

6,553.5

0.0

Line Voltage

69

Volts

1

0

9999

480

Motor FLC

70

Amps

10

1.0

999.9

1.0

Service

Factor

84

100

0.01

1.99

1.15

Motor Code

Letter

72

A, B, C, D, E, F, G, H, J, K, L,

M, N, P, R, S, T, U, and V

G

LRC Ratio

81

10

0.0

19.9

0.0

Converter

Rating

74

None, 20, 180, 630

None

CT Ratio

75

5, 50, 75, 100, 150, 200,

250, 300, 400, 500, 600, 750,

800, 1000, 1200 :5

5:5

Calibration

76

Off, Activate

Off

Enter Calib.

Amps

77

Amps

0.01

999.9

0.0

Current

Phase A

4

Amps

10

Parameter

Mgmt.

17

Ready, Default Init.

Recll Frm EE,Store In EE

Ready