Remote i/o examples (cont.) – Rockwell Automation 150 USE MN/SMC DIALOG + CONTROLLER User Manual

Page 115

Advertising
background image

8-6

Serial Communications

Remote I/O Examples (cont.)

1203-GD1 Communication Module Switch Settings

The following information is provided to explain the required 1203-
GD1 communication module switch settings for this example. Refer
to the 1203-GD1 manuals for further details related to the switch
settings.

Example Information

This configuration requires a 1/4 rack size allocation.

The SMC Dialog Plus controller does not support Datalinks.

Switch Settings

Description

Switch Setting

SMC Rack Address:

02

SW1: Switches 1 & 2 (Not Used), Switches
3-6 & 8 (On), Switch 7 (Off)

Starting Group Address:

0

SW2: Switches 1 & 2 (On)

Last Rack:

No

SW2: Switch 3 (Off)

Hold Last State:

Yes

SW2: Switch 4 (On)

Fault on Comm Loss:

Yes

SW2: Switch 5 (On)

Fault Controller:

No

SW2: Switch 6 (Off)

R I/O Baud Rate:

115k

SW2: Switch 7 (On), Switch 8 (Off)

Block Transfer:

No

SW3: Switch 1 (Off)

Logic Cmd/Status:

Yes

SW3: Switch 2 (On)

Reference/Feedback:

Yes

SW3: Switch 3 (On)

Datalinks:

No

①②

SW3: Switch 4-8 (Off)

SW

1

8

7 6

5 4

3

2

1

Not Used

Not Used

On

On

On

On

Off

On

SW

2

8

7 6

5 4

3

2

1

Starting Module Group (0)

Starting Module Group (0)

Last Rack Setting (Off)

Hold Last State (On)
Fault on Comm Loss (On)

Fault Controller (Off)

R I/O Baud Rate (115k)

R I/O Baud Rate (115k)

SW

3

8

7 6

5 4

3

2

1

Block Transfer On

Logic Cmd/Sts On

Reference/Fdbk Off

Datalink A Off

Datalink B Off

Datalink C Off

Datalink D Off

Truncate Last Datalink Off