Channel configuration worksheet – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 108

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

B-4 NT4 Configuration Worksheet

Channel Configuration
Worksheet

Input Type Select

Data Format Select

Open Circuit Select

Temperature Units Select

Filter Frequency Select

Channel Enable

Not Used

Channel 0

Channel 1

Channel 2

Channel 3

11

0

0

0

0

9

10

8

6

7

4

5

0

1

2

3

0

0

0

0

0

0

0

0

0

0

0

0

Bit Number

15

12

13

14

Bit Definitions:

Description

Specification

Bits 0-3

Input Type Select

0000 = J
0001 = K
0010 = T
0011 = E

0100 = R
0101 = S
0110 = B
0111 = N

1000 = ±50 mV
1001 = ±100 mV
1111 = CJC temperature

Bits 4 and 5

Data Format Select

00 = engineering units, x1 (0.1°/step,
0.01 mV/step)

01 = engineering units, x10 (1°/step,
0.1 mV/step)

10 = scaled-for-PID (0 to 16383)

11 = proportional counts (-32768 to
+32767)

Bits 6 and 7

Open Circuit Select

00 = zero

01 = upscale

10 = downscale

Bit 8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit

Bits 9 and 10

Filter Frequency Select

00 = 10 Hz

01 = 50 Hz

10 = 60 Hz

11 = 250 Hz

Bit 11

Channel Enable

0 = channel disabled

1 = channel enabled

Bits 12-15

Not Used

0000 = always make this setting