Channel cut-off frequency -5, Channel cut-off frequency – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 47

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

Preliminary Operating Considerations 4-5

Channel Cut-Off Frequency

The channel filter frequency selection determines a channel’s cut-off
frequency, also called the -3 dB frequency. The cut-off frequency is
defined as the point on the input channel frequency response curve
where frequency components of the input signal are passed with 3 dB
of attenuation. All frequency components at or below the cut-off
frequency are passed by the digital filter with less than 3 dB of
attenuation. All frequency components above the cut-off frequency
are increasingly attenuated, as show in the graphs starting below.

The cut-off frequency for each input channel is defined by its filter
frequency selection. The table on the previous page lists the input
channel cut-off frequency for each filter frequency. Choose a filter
frequency so that your fastest changing signal is below that of the
filter’s cut-off frequency. The cut-off frequency should not be
confused with update time. The cut-off frequency relates how the
digital filter attenuates frequency components of the input signal. The
update time defines the rate at which an input channel is scanned and
its channel data word updated.

200

180

160

140

120

100

80

60

40

20

0

0

60

120

180

240

300

60 Hz Filter Notch Frequency
Frequency Response

Amplitude (in dB)

Frequency

15.72 Hz

-3 dB

Hz