7-2 Module Diagnostics and Troubleshooting

Channel Diagnostics

When a channel is enabled (bit 11 = 1), a diagnostic check is
performed to see that the channel has been properly configured. In
addition the channel is tested for out-of-range and open-circuit faults
on every scan. If the channel is configured for thermocouple input or
CJC input, the CJC sensors are also checked for out-of-range and open
circuits.

A failure of any channel diagnostic test causes the faulted channel
status LED to blink. All channel faults are indicated in bits 12-15 of the
channel’s status word. Channel faults are self-clearing, and the
channel LED will stop blinking and resume steady illumination when
the fault conditions are corrected.

IMPORTANT

If you clear (0) a channel enable bit (11) all channel
status information is reset.