Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 66

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

5-14 Channel Configuration, Data, and Status

Bit(s)

Define

These bit settings

Indicate this

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0–3

Input type

0

0

0

0

Thermocouple Type J

0

0

0

1

Thermocouple Type K

0

0

1

0

Thermocouple Type T

0

0

1

1

Thermocouple Type E

0

1

0

0

Thermocouple Type R

0

1

0

1

Thermocouple Type S

0

1

1

0

Thermocouple Type B

0

1

1

1

Thermocouple Type N

1

0

0

0

50 mV

1

0

0

1

100 mV

1

0

1

0

Invalid

1

0

1

1

Invalid

1

1

0

0

Invalid

1

1

0

1

Invalid

1

1

1

0

Invalid

1

1

1

1

CJC temperature

4 and 5

Data type 1

0

0

Engineering units x 1

(2)

0

1

Engineering units x 10

(2)

1

0

Scaled–for–PID

1

1

Proportional Counts

6 and 7

Open circuit type

0

0

Zero

0

1

Upscale

1

0

Downscale

1

1

Invalid

8

Temperature units
type

(1)

0

Degrees C

1

Degrees F

9 and 10

Channel filter
frequency

0

0

10 Hz

0

1

50 Hz

1

0

60 Hz

1

1

250 Hz

11

Channel status

0

Channel Disabled

1

Channel Enabled

12

Open–circuit error

0

No error

1

Open circuit detected

13

Under–range error

0

No error

1

Under–range condition

14

Over–range error

0

No error

1

Over–range condition

15

Configuration error

0

No error

1

Configuration error

(1)

When millivolt input type is selected, the bit setting for temperature units is ignored.

(2)

For engineering units x1, values are expressed in 0.1 degrees or 0.01 mV. For engineering units x10, values are expressed in 1.0 degrees or 0.1 mV.

Advertising