Channel configuration -2, Channel configuration – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 88

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

8-2 Application Examples

Channel Configuration

Configure the thermocouple channel with the following setup:

type J thermocouple

°F - display to whole degree

zero data word in the event of an open circuit

10 Hz input filter to reject high frequency noise and give good
rejection of 60 Hz line noise

Channel Configuration Worksheet (With Settings Established for Channel 0)

Input Type Select

Data Format Select

Open Circuit Select

Temperature Units Select

Filter Frequency Select

Channel Enable

Not Used

Channel 0

Channel 1

Channel 2

Channel 3

11

0

0

1

0

0

0

0

9

10

8

1

6

7

0

0

0

1

4

5

0

0

0

0

0

1

2

3

0

0

0

0

0

0

0

0

0

0

0

0

Bit Number

12

13

14

15


Bits:

0-3

Input Type Select

0000 = J
0001 = K
0010 = T
0011 = E

0100 = R
0101 = S
0110 = B
0111 = N

1000 = ±50 mV
1001 = ±100 mV
1111 = CJC temperature

4 and 5

Data Format Select

00 = engineering units, x1 (0.1°/step,
0.01 mV/step)

01 = engineering units, x10 (1°/step,
0.1 mV/step)

10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)

6 and 7

Open Circuit Select

00 = zero

01 = upscale

10 = downscale

8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit

9 and 10

Filter Frequency Select

00 = 10 Hz

01 = 50 Hz

10 = 60 Hz

11 = 250 Hz

11

Channel Enable

0 = channel disabled

1 = channel enabled

12-15

Not Used

0000 = always make this setting