Publication 1746-UM007C-EN-P - July 2004

3-10 Installation and Wiring

If it is necessary to connect the shield at the module, each input
channel has a convenient shield connection screw terminal that
provides a connection to chassis ground. All shields are
internally connected, so any shield terminal can be used with
channels 0-3. For maximum noise reduction, one shield terminal
must be connected to earth ground potential, i.e. mounting bolt
on 1746 chassis.

Tighten terminal screws using a flat or cross-head screwdriver.
Each screw should be turned tight enough to immobilize the
wire’s end. Excessive tightening can strip the terminal screw.
The torque applied to each screw should not exceed 5 lb-in
(0.565 Nm) for each terminal.

The open thermocouple detection circuit injects approximately
12 nanoamperes into the thermocouple cable. A total lead
resistance of 25 ohms (12.5 one-way) will produce 0.3 mV of
error. To reduce error, use large gage wire with less resistance
for long wire runs.

Follow system grounding and wiring guidelines found in your
SLC 500 Modular Hardware Style User Manual (publication
1747-UM011).