Installation and Wiring 3-9

To ensure proper operation and high immunity to electrical
noise, always use Belden

8761 (shielded, twisted pair) or

equivalent wire for millivolt sensors or shielded, twisted pair
thermocouple extension lead wire specified by the
thermocouple manufacturer for the thermocouple type you are
using. Using the incorrect thermocouple extension wire type or
not following the correct polarity convention will cause invalid
readings.

Special considerations for using the analog common
(

ANALOG COM

) terminal based on thermocouple type:

(See Appendix D for definitions of thermocouple types.)

When using grounded thermocouple(s), jumper the

ANALOG

COM

terminal to any single active grounded channel’s plus (+)

or minus (-) terminal.

When using exposed thermocouple(s) that have the

thermocouple junction touching an electrically conductive
material, jumper the

ANALOG COM

terminal to any single active

exposed channel’s plus (+) or minus (-) terminal.

When using ungrounded (shielded) or exposed

thermocouples that are not touching an electrically
conductive material, do not use the

ANALOG COM

terminal.

When using a mix of grounded, ungrounded and exposed

thermocouples, jumper the

ANALOG COM

terminal to any

single active grounded channel’s plus (+) or minus (-)
terminal.

I

f millivolt inputs are used, the terminal should be handled as

discussed on page 1-7.

The Series A 1746-NT4 does not have an

ANALOG COM

terminal and cannot be used with multiple grounded and/or
exposed thermocouples that touch electrically conductive
material. The Series A can be used with a single grounded
and/or exposed thermocouple that touches electrically
conductive material, or multiple grounded thermocouples that
have the protective sheath made of an electrically
non-conductive material such as ceramic.

Ground the shield drain wire at one end only. The preferred
location is to the same point as the sensor ground reference.

For grounded thermocouples or mV sensors, this is at the

sensor.

For insulated/ungrounded thermocouples, this is at the

module.

(Refer to IEEE Std. 518, Section 6.4.2.7 or contact your sensor

manufacturer for additional details.)