Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 95

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

Application Examples 8-9

0

Rung 2.4

Degrees
Selector Switch -
Celsius

]/[

I:2.0

If the ambient/cabinet selector switch is turned to the ambient position and the degrees selector
switch is in the Celsius position, configure channel 0 to read the ambient temperature
thermocouple in degrees Celsius.

OSR

B3

4

Configure NT4
Channels

MOVE
Source N10:4

Dest

O:1.0

1

I:2.0

] [

Ambient/Cabinet
Selector Switch -
Ambient

MOV

0

Rung 2.5

Degrees
Selector Switch -
Celsius

] [

I:2.0

If the ambient/cabinet selector switch is turned to the cabinet position and the degrees selector
switch is in the Celsius position, configure channel 0 to read the CJC sensor on the NT4 module in
degrees Celsius.

OSR

B3

5

Configure NT4
Channels

MOVE
Source N10:9

Dest

O:1.0

1

I:2.0

]/[

Ambient/Cabinet
Selector Switch -
Cabinet

MOV

Rung 2.6

If channel 0 is set up for reading the ambient thermocouple, energize the ambient pilot light on
the annunciator panel.

Ambient Light

MASKED EQUAL
Source I:1.4

Mask

FEFF

Compare

N1

0:4

( )

O:7.0

0

MEQ

Rung 2.7

If channel 0 is set up for reading the CJC sensor on the NT4 module, energize the cabinet pilot
light on the annunciator panel.

Cabinet Light

MASKED EQUAL
Source I:1.4

Mask

FEFF

Compare

N10:9

( )

O:7.0

1

MEQ