2-4 Quick Start for Experienced Users

4.

Connect the thermocouple wires

Reference

Connect thermocouple wires to channel 0 on the module’s terminal block. Make sure both cold
junction compensation (CJC) assemblies are securely attached.

Ground the shield drain wire at one end only. The preferred location is to the same point as the
sensor ground reference. For grounded thermocouples or mV sensors, this is at the sensor. For
insulated/ungrounded thermocouples, this is at the NT4 module.

Chapter 3
(Installion and
Wiring

Appendix D
(Thermocouple
Types

CHL 0

CJC A
Assembly

CHL 0+

Thermocouple
Wire

Terminal Block

SHIELD

SHIELD

CHL 1+

CHL 1

Refer to the paragraph above

_

_

5.

Configure the system.

Reference

Configure your system I/O configuration for the particular slot the NT4 is in (slot 1 in this
example). Select the module from the drop-down list or enter the thermocouple input module ID
code (3510).

When using RSLogix 500 version 6.10 or higher, you may select Advanced Configuration, then
Configure, to use the software’s I/O wizard to configure the NT4 (see appendix E for details). If
you use this option, proceed to step 8.

Chapter 4
(Preliminary
Operating
Considerations)

Your
programming
software online
help screens