8-6 Application Examples

Channel Configuration Worksheet (With Settings Established)

Input Type Select

Data Format Select

Open Circuit Select

Temperature Units Select

Filter Frequency Select

Channel Enable

Not Used

Channel 0

Channel 1

Channel 2

Channel 3

11

1

0

1

0

0

0

0

9

10

8

x

6

7

0

0

0

0

4

5

0

0

1

0

0

1

2

3

0

0

0

0

0

0

0

0

0

0

0

0

Bit Number

(Ambient)

(Bath)

(Steam)

(Chilled
H2O)

1

0

1

1

0

1

1

0

1

x

x

x

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

12

13

14

15







Bits:

0-3

Input Type Select

0000 = J
0001 = K
0010 = T
0011 = E

0100 = R
0101 = S
0110 = B
0111 = N

1000 = ±50 mV
1001 = ±100 mV
1111 = CJC temperature

4 and 5

Data Format Select

00 = engineering units, x1 (0.1°/step,
0.01 mV/step)
01 = engineering units, x10 (1°/step,
0.1 mV/step)

10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)

6 and 7

Open Circuit Select

00 = zero

01 = upscale

10 = downscale

8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit

9 and 10

Filter Frequency Select 00 = 10 Hz

01 = 50 Hz

10 = 60 Hz

11 = 250 Hz

11

Channel Enable

0 = channel disabled

1 = channel enabled

12-15

Not Used

0000 = always make this setting