6-2 Ladder Programming Examples

Example - Configure four channels of a thermocouple module
residing in slot 3 of a 1746 chassis. Configure each channel with the
same parameters.

This example transfers configuration data and sets the channel enable
bits of all four channels with a single File Copy instruction.

Procedure

1. Create integer file N10. Integer file N10 should contain four

elements (N10:0 through N10:3).

2. Enter the configuration parameters for all four thermocouple

channels into a source integer data file N10. See Appendix B for
a channel configuration worksheet.

3. Program a rung in your ladder logic to copy the contents of

integer file N10 to the four consecutive output words of the
thermocouple module beginning with O:3.0.

11

0

0

1

Type K Thermocouple Input

Engineering Units 10

Zero If Open Circuit

Fahrenheit

10 Hz Filter Frequency

Channel Enable Bit

Not Used

Bit Number

Bit Setting

Configures Channel For:

0

0

0

0

9

10

8

1

6

7

0

0

0

1

4

5

0

0

0

1

0

1

2

3

15

14

13

12






] [

COP

COPY FILE
Source #N10:0
Dest

#O:3.0

Length 4

First Pass Bit

S:1

15

On power up, bit S:1/15 is set for the first program scan, and integer file N10
is sent to the NT4 channel configuration words.

Initialize NT4