Dynamic programming, Dynamic programming -3 – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 73

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

Ladder Programming Examples 6-3

Dynamic Programming

The following example explains how to change data in the channel
configuration word when the channel is currently enabled.

Example - Execute a dynamic configuration change to channel 2 of
the thermocouple module located in slot 3 of a 1746 chassis. Change
from monitoring an external type K thermocouple to monitoring the
CJC sensors mounted on the terminal block. This gives a good
indication of what the temperature is inside the control cabinet.
Finally, set channel 2 back to type K thermocouple.

Program Listing

] [

COP

COPY FILE
Source

#N10:0

Dest

#O:3.0

Length 4

S:1

15

Set up all four channels

Rung 2:0

] [

0

Set channel 2 to CJC

Rung 2:1

B3

0

I:1.0

MOVE
Source

N10:4

Dest

O:3.2

MOV

[OSR]

Rung 2:2

B3

1

]/[

MOVE
Source

N10:2

Dest

O:3.2

Set channel 2 back to type K

MOV

0

I:1.0

[OSR]

Rung 2:3

END

Data Table

address 15 data 0 address 15 data 0

N10:0 0000 1001 0001 0001 N10:3 0000 1001 0001 0001

N10:1 0000 1001 0001 0001 N10:4 0000 1001 0001 1111

N10:2 0000 1001 0001 0001

IMPORTANT

While the module performs the configuration
alteration, it does not monitor input device data
change at any channel. Refer to page 4-9, Channel
Turn-On, Turn-Off, and Reconfiguration Times.