Publication 1746-UM007C-EN-P - July 2004

5-8 Channel Configuration, Data, and Status

Proportional Counts to Engineering Units

Equation: Engr Units Equivalent = SLOW + { (SHIGH - SLOW)
x [ ( Proportional Counts value displayed + 32768) / 65536 ] }

Assume type E input type, proportional counts display type,
channel data = 21567.

Want to calculate °F equivalent.

From Channel Data Word Format table, SLOW = -454°F and
SHIGH = 1832°F.

Solution: Engr Units Equivalent = -454°F + { [1832°F - (-454°F) ]
x [ ( 21567 + 32768) / 65536 ] } = 1441.3°F

Engineering Units to Proportional Counts

Equation: Proportional Counts Equivalent = { 65536 x [ ( Engineering
Units desired - SLOW ) / ( SHIGH - SLOW ) ] } - 32768

Assume type E input type, proportional counts display type,
desired channel temp. = 1000°F.

Want to calculate Proportional Counts equivalent.

From Channel Data Word Format table, SLOW = -454°F and
SHIGH = 1832°F.

Solution: Proportional Counts Equivalent = { 65536 x [ ( 1000°F -
(-454°F) ) / (1832°F - (-454°F ) ) ] } - 32768 = 8916.