Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 25

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

Quick Start for Experienced Users 2-5

6.

Determine the operating parameters.

Reference

Determine the operating parameters for channel 0. This example shows the channel 0
configuration word defined with all defaults (0) except for channel enable (bit 11). The
addressing reflects the location of the module as slot 1.

Chapter 4
(Preliminary
Operating
Considerations)

Chapter 5
(Channel
Configuration,
Data, and
Status)

Appendix B
(NT4
Configuration
Worksheet)

O:1.1

Channel 1 Configuration Word

Channel 2 Configuration Word

Channel 3 Configuration Word

Words 4 7

(not defined)

Output Image

SLC 500 Controller
Data Files

Bit 15

Bit 0

Word 1

Word 2

Word 3

Address

O:1.0

Input Image

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Configuration Word

Word 0

Word 7

Input

Type

Data Format

Open Circuit

Temperature Units

Filter Frequency

Channel Enable

Unused

(8 words)

0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

Default Setting

New Setting

Set this bit (11) to enable channel.

Address = O:1.0/11.

Type J Thermocouple

Engineering Units x 1

Data Word = 0 If Open Circuit

Degrees Celsius

10 Hz. Filter Frequency

Channel Disabled

O:1.2
O:1.3

O:1.7