Preliminary Operating Considerations 4-7

Update Time

The thermocouple module update time is defined as the time required
for the module to sample and convert the input signals of all enabled
input channels and make the resulting data values available to the SLC
processor. It can be calculated by adding the the sum of all enabled
channel sample times, plus a CJC update time.

The NT4 module sequentially samples the channels in a continuous
loop.

The following table shows the channel sampling times for each filter
frequency. It also gives the CJC update time.

The fastest module update time occurs when only one channel with a
250 Hz filter frequency is enabled.

Module update time = 12 ms + 14 ms = 26 ms

The slowest module update time occurs when four channels, each
using a 10 Hz filter frequency (4 * 300 = 1200), are enabled.

Module update time = 1200 ms + 14 ms = 1.214 seconds

Channel 0 Disabled

Channel 1 Disabled

Channel 2 Disabled

Channel 3 Disabled

Sample
Channel 0

Sample
Channel 1

Sample
Channel 2

Sample
Channel 3

Enabled

Enabled

Enabled

Enabled

Update CJC

Calculate Previous

Calculate Previous

Calculate Previous

Calculate Previous

Sample
CJC
Channels

CJC Update
Time

Channel Sampling Time

250 Hz Filter 60 Hz Filter

50 Hz Filter

10 Hz Filter

14 msec

12 msec

50 msec

60 msec

300 msec