3-8 Installation and Wiring

Replacing a Series A thermocouple module with a Series B module
requires that the bottom right terminal (which was SHIELD on Series A
modules) no longer be connected to CHASSIS GROUND if it was
previously. Use one of the other SHIELD terminals.

Wiring Considerations

Follow the guidelines starting below when planning your system
wiring.

To limit noise, keep thermocouple and millivolt signal wires as
far away as possible from power and load lines.

ATTENTION

The possibility exists that grounded or exposed
thermocouples can become shorted to a potential
greater than that of the thermocouple itself. Due to
possible shock hazard, care should be taken when
wiring these types of thermocouples. Refer to
Appendix D for more details.