4-8 Preliminary Operating Considerations

Update Time Calculation Example

The following example shows how to calculate the module update
time for the given configuration:

channel 0 configured for 250 Hz filter frequency, enabled

channel 1 configured for 250 Hz filter frequency, enabled

channel 2 configured for 50 Hz filter frequency, enabled

channel 3 disabled

Using the values from the table above, add the the sum of all enabled
channel sample times, plus one CJC update time.

channel 0 sampling time = 12 ms

channel 1 sampling time = 12 ms

channel 2 sampling time = 60 ms

CJC update time = 14 ms

Module update time = 12 + 12 + 60 + 14 = 98 ms