Linear Millivolt Device Compatibility

A large number of millivolt devices may be used with the 1746-NT4
module. For this reason we do not specify compatibility with any
particular device.

However, millivolt applications often use bridges of strain gages. To
allow the NT4 Series B (or higher) to operate correctly, the analog
common (

ANALOG COM

) terminal of the module needs to be biased to a

level within 2V of the signal of interest. A resistive voltage divider
using 10k

resistors is recommended to accomplish this. The circuit

diagram below shows how this connection is made.

ATTENTION

The possibility exists that grounded or exposed
thermocouples can become shorted to a potential
greater than that of the thermocouple itself. Due to
possible shock hazard, care should be taken when
wiring these types of thermocouples. Refer to
Appendix D for more details.

+

-

ANALOG COM

fixed

fixed

variable

fixed

INPUT

(CHL0, CHL1,

CHL2, CHL3)

Vcc

+

10k

10k

NT4

Strain

Gage

Bridge