Publication 1746-UM007C-EN-P - July 2004

Channel Configuration, Data, and Status 5-11

Select Temperature Units (Bit 8)

The temperature units bit lets you select temperature engineering
units for thermocouple and CJC input types. Units are either degrees
Celsius (°C) or degrees Fahrenheit (°F). This bit field is only active for
thermocouple and CJC input types. It is ignored when millivolt inputs
types are selected.

Select Channel Filter Frequency (Bits 9 and 10)

The channel filter frequency bit field lets you select one of four filters
available for a channel. The filter frequency affects the channel update
time and noise rejection characteristics. A smaller filter frequency
increases the channel update time, but also increases the noise
rejection and channel resolution. A larger filter frequency decreases
the noise rejection, but also decreases the channel update time and
channel resolution.

250 Hz setting provides minimal noise filtering.

60 Hz setting provides 60 Hz AC line noise filtering.

50 Hz setting provides 50 Hz AC line noise filtering.

10 Hz setting provides both 50 Hz and 60 Hz AC line noise
filtering.

When a CJC input type is selected, this field is ignored.

IMPORTANT

If you use engineering units (1 mode) and
Fahrenheit temperature units (i.e. 0.1°F), the full
scale temperature for thermocouple type B is not
achievable with 15-bit numerical representation. An
over range error will occur for that channel if it tries
to represent the full scale value. The maximum
representable temperature is 3276.7°F (instead of
3308°F).