Channel Configuration, Data, and Status 5-7

Scaling Examples

Scaled-for-PID to Engineering Units

Equation: Engr Units Equivalent = SLOW + [ (SHIGH - SLOW) x
(Scaled-for-PID value displayed / 16384) ]

Assume type J input type, scaled-for-PID display type, channel
data = 3421.

Want to calculate °C equivalent.

From Channel Data Word Format table, SLOW = -210°C and
SHIGH = 760°C.

Solution: Engr Units Equivalent = -210°C + [ (760°C - (-210°C) ) x
(3421 / 16384) ] = -7.46°C.

Engineering Units to Scaled-for-PID

Equation: Scaled-for-PID Equivalent = 16384 x [ (Engineering Units
desired - SLOW) / ( SHIGH - SLOW ) ]

Assume type J input type, scaled-for-PID display type, desired
channel temp. = 344°C.

Want to calculate Scaled-for-PID equivalent.

From Channel Data Word Format table, SLOW = -210°C and
SHIGH = 760°C.

Solution: Scaled-for-PID Equivalent = 16384 x [ (344°C - (-210°C) )
/ ( 760°C - (-210°C ) ) ] = 9357.