Led indicators, Led indicators -3 – Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 81

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

Module Diagnostics and Troubleshooting 7-3

LED Indicators

The thermocouple module has five LEDs. Four of these are channel
status LEDs numbered to correspond to each of the thermocouple’s
input channels, and one is a module status LED.

If
Module
Status
LED is:

And
Channel
Status
LED is:

Indicated Condition: Corrective action:

On

On

Channel Enabled

No action required.

Blinking

Open Circuit Condition To determine the exact error, check the

error bits in the input image. Check the
channel configuration word for valid data.
Make sure that the input type is indicated
correctly in bits 0-3, and that the open
circuit selection state (bits 6 and 7) is valid.
Refer to the troubleshooting flowchart on
page 7-6 and chapter 5 for more
information.

Out-of-Range
Condition

Channel Configuration
Error

Off

Power-Up

No action required.

Channel Not Enabled

No action required. For an example of how
to enable a channel refer to chapter 2,
Quick Start for Experienced Users, or
chapter 6, Programming Examples.

If Module
Status
LED is:

Indicated condition:

Corrective action:

On

Proper Operation

No action required.

Off

Module Fault

Cycle power. If condition persists, call your local
distributor or Rockwell Automation for assistance.

0

1

2

3

INPUT

Channel LEDs

Module Status LED

MODULE STATUS

CHANNEL

THERMOCOUPLE/mV

STATUS

Advertising