4-10 Preliminary Operating Considerations

Response to Slot Disabling

By writing to the status file in your modular SLC processor you can
disable any chassis slot. Refer to your programming device‘s manual
for the slot disable/enable procedure.

Input Response

When a thermocouple slot is disabled, the thermocouple module
continues to update its input image table. However, the SLC processor
does not read inputs from a module that is disabled. Therefore, when
the processor disables the thermocouple module slot, the module
inputs appearing in the processor image table remain in their last
state, and the module’s updated image table is not read. When the
processor re-enables the module slot, the current state of the module
inputs are read by the processor during the subsequent scan.

Output Response

The SLC processor may change the thermocouple module output data
(configuration) as it appears in the processor output image. However,
this data is not transferred to the thermocouple module. The outputs
are held in their last state. When the slot is re-enabled, the current
data in the processor image is transferred to the thermocouple
module.

ATTENTION

Always understand the implications of disabling a
thermocouple module before using the slot disable
feature.