Rockwell Automation 1746-NT4 Series B,D17466.6.1 SLC 500 4-Channel Thermocouple/mV Input Module User Manual User Manual

Page 56

Advertising
background image

Publication 1746-UM007C-EN-P - July 2004

5-4 Channel Configuration, Data, and Status

Bit(s)

Define

To Select

Make these bit settings in the Channel Configuration Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0-3

Input type

Thermocouple Type J

0

0

0

0

Thermocouple Type K

0

0

0

1

Thermocouple Type T

0

0

1

0

Thermocouple Type E

0

0

1

1

Thermocouple Type R

0

1

0

0

Thermocouple Type S

0

1

0

1

Thermocouple Type B

0

1

1

0

Thermocouple Type N

0

1

1

1

50mV

1

0

0

0

100mV

1

0

0

1

Invalid

1

0

1

0

Invalid

1

0

1

1

Invalid

1

1

0

0

Invalid

1

1

0

1

Invalid

1

1

1

0

CJC temperature

1

1

1

1

4 and 5

Data format

Engineering units x 1

(2)

0

0

Engineering units x 10

(2)

0

1

Scaled–for–PID

1

0

Proportional Counts

1

1

6 and 7

Open circuit

Zero

0

0

Upscale

0

1

Downscale

1

0

Invalid

1

1

8

Temp

(1)

Degrees C

0

Degrees F

1

9 and 10

Channel filter
frequency

10 Hz

0

0

50 Hz

0

1

60 Hz

1

0

250 Hz

1

1

11

Channel
enable

Channel Disabled

0

Channel Enabled

1

12-15

Unused

Unused

0

0

0

0

(1) When millivolt input type is selected, the bit setting for temperature units is ignored.

(2) For engineering units x1, values are expressed in 0.1 degrees or 0.01 mV. For engineering units x10, values are expressed in 1.0 degrees or 0.1 mV.