8-8 Application Examples

0

Rung 2.0

] [

I:2.0

If the degrees selector switch is turned to the Fahrenheit position, set up all four channels to read in
degrees Fahrenheit. The default for channel 0 is to read the ambient temperature thermocouple.

OSR

B3

0

Configure NT4
Channels

COPY FILE
Source #N10:0
Dest

#O:1.0

Length 4

COP

Degrees
Selector Switch -
Fahrenheit

0

Rung 2.1

] [

I:2.0

If the ambient/cabinet selector switch is turned to the ambient position and the degrees selector
switch is in the Farenheit position, configure channel 0 to read the ambient temperature
thermocouple in degrees Fahrenheit.

OSR

B3

1

Configure NT4
Channels

MOVE
Source N10:0

Dest

O:1.0

1

I:2.0

] [

Ambient/Cabinet
Selector Switch -
Ambient

MOV

Degrees
Selector Switch -
Fahrenheit

0

Rung 2.2

Degrees
Selector Switch -
Fahrenheit

] [

I:2.0

If the ambient/cabinet selector switch is turned to the cabinet position and the degrees selector
switch is in the Farenheit position, configure channel 0 to read the CJC sensor on the NT4 module
in degrees Fahrenheit.

OSR

B3

2

Configure NT4
Channels

MOVE
Source N10:8

Dest

O:1.0

1

I:2.0

]/[

Ambient/Cabinet
Selector Switch -
Ambient

MOV

0

Rung 2.3

Degrees
Selector Switch -
Celsius

]/[

I:2.0

If the degrees selector switch is turned to the Celsius position, set up all four channels to read in
degrees Celsius. The default for channel 0 is to read the ambient temperature thermocouple.

OSR

B3

3

Configure NT4
Channels

COPY FILE
Source #N10:4
Dest

#O:1.0

Length 4

COP