I:e.3 rate measurement (hz), I:e.4 output status, configuration error code, I:e.4 bits 0 through 7 - configuration error code – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 103

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

Configuration and Programming 4-43

I:e.3 Rate Measurement (Hz)

This word indicates the current rate at which the count is being
received (in Hz). This value is updated after every Rate Period.

This input value is active in all modes. When the module is used with
encoders and configured for x2 or x4 input types, the calculated value
will be scaled down by a factor or two or four respectively.

I:e.4 Output Status, Configuration Error Code

I:e.4 Bits 0 through 7 - Configuration Error Code

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Rate Measurement Word 3

I:e.3

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Output Status and Configuration Error Code, Word 4

I:e.4

Physical Outputs 0–3

Configuration Error Code

Soft Outputs 4–7

Configuration
Error Code

Reason

Critical
Error

Action

Hex Binary

01

0000 0001 not defined

-

reconfigure

(1)

(1) The Function Control bit must be reset to 0, the parameter must be changed, and the Function Control bit is

then set to 1

.

02

0000 0010 max count = 0 (ring)

yes

reconfigure

(1)

03

0000 0011 invalid operating mode

yes

reconfigure

(1)

04

0000 0100 invalid input type

yes

reconfigure

(1)

05

0000 0101 static parameter changed

yes

reconfigure

(1)

06

0000 0110 ranges active = 0

no

change parameter

07

0000 0111 rate period = 0

no

change parameter

08

0000 1000 linear counter reset value out of range

no

change parameter

09

0000 1001 sequencer preset > max. count

no

change parameter