3-8 Installation and Wiring

Outputs

The module provides four Physical Outputs. They can be controlled
by the module when certain counter conditions are met, or they can
be controlled from the user program (refer to M0:e.0 in Chapter 4).

The outputs are bipolar transistors connected in a sinking (open collector
sinking) configuration. When the output is energized, it sinks the current.

You can select an output voltage range of 4.5-10V dc or 10-30V dc.
Refer to Appendix A for the maximum current specs for each voltage
range. Dip switch SW2, located on the PC board, is used to select the
voltage range. The figure below identifies the switches and indicates
how to set them.

The figure below indicates wiring connections for four 24V dc
outputs. Switches of SW2 are OFF for this output voltage.

The outputs are not electrically isolated from each other. (They are
referenced to the same output common terminal.) However, outputs
are isolated from the rest of the circuitry to a level of 1500 volts.

Switch

1

2

3

4

Position

Output voltage range

Output

0

1

2

3

ON
OFF

4.5-10V dc
10-30V dc

ATTENTION

All switches of SW2 must be ON or all switches must
be OFF. Permanent damage may result if some are
ON and some are OFF.

1 2 3 4

ON

OFF

Dip switch SW2

ON postion

OFF postion

OUT 0

OUT 1

OUT 2

OUT 3

VDC

DC COM

wiring terminals

+

HSCE module

1 2 3 4

ON

OFF

Dip switch SW2

User Supplied

24V dc