Input data file words - sequencer mode, I:e.0 status word, Input data file words - sequencer mode -37 – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 97: I:e.0 status word -37, I:e.0 bits 0 and 1, Bits 0 and 1 are reserved and must be reset to 0

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

Configuration and Programming 4-37

Input Data File Words -
Sequencer Mode

The figure below shows how the input data file words are used. An
explanation of each word follows the figure.

I:e.0 Status Word

I:e.0 Bits 0 and 1

Bits 0 and 1 are reserved and must be reset to 0.

Status Word, Word 0

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

I:e.0

Accumulated Count, Word 1

Rate Period Count, Word 2

Rate Measurement Word 3

Output Status and Configuration Error Code, Word 4

Next Sequencer Step and Current Sequencer Step Word 5

Reserved, Word 6

Next Sequencer Step Preset, Word 7

I:e.1
I:e.2
I:e.3
I:e.4
I:e.5
I:e.6
I:e.7

Physical Outputs

Configuration Error Code

Soft Outputs

Next
Sequencer
Step

Current
Sequencer Step

R

R

R R R R R

R

R R

R R R R R

R

R R

R

R

R

0 = No configuration error
1 = Invalid configuration data

0 = No overflow
1 = Overflow

0 = Nonzero Rate Period Count
1 = Rate Period Count is 0

0 = Invalid rate
1 = Rate valid

0 = No overflow
1 = Overflow

0 = No errors detected
1 = Error detected

0 = No error detected
1 = Overflow/Underflow

00 = Stopped
01 = Running
10 = Undefined
11 = Hold

0 = False Reset Mode
1 = True Reset Mode

Status Word, Word 0

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

I:e.0

Zero Rate Period Count

Rate V

alid

Rate Counter Overflow

Rate Measurement Overflow

Critical Error

Configuration Error

Pulse Counter State

Overflow/Underflow

Reset Input

R

1 = End of sequence

Sequence Done

R

R

R

R