M0 and M1 Files B-7

Minimizing the Scan Time

You can keep the processor scan time to a minimum by economizing
on the use of instructions addressing the M0 or M1 files. For example,
XIC instruction M0:2.1/1 is used in rungs 1 and 2 of the figure below,
adding approximately 2 ms to the scan time if you are using a SLC
5/02 Series B processor.

In the equivalent rungs of the figure below, XIC instruction M0:2.1/1
is used only in rung 1, reducing the SLC 5/02 scan time by
approximately 1 ms.

The figure below illustrates another economizing technique. The COP
instruction addresses an M1 file, adding approximately 4.29 ms to the
scan time if you are using a SLC 5/02 Series B processor. Scan time
economy is realized by making this rung true only periodically, as
determined by clock bit S:4/8. A rung such as this might be used
when you want to monitor the contents of the M1 file, but monitoring
need not be on a continuous basis.

XIC instructions in rungs 1 and 2 are addressed to the M0 data file. Each of
these instructions adds approximately 1 ms to the scan time (SLC 5/02
Series B processor).

1

] [

B3

12

] [

M0:2.1

1

( )

B3

14

] [

M0:2.1

1

( )

B3

10

2

These rungs provide equivalent operation to those of figure A by substituting
XIC instruction B3/10 for XIC instruction M0:2.1/1 in rung 2. Scan time is
reduced by approximately 1 ms (SLC 5/02 Series B processor).

] [

B3

12

] [

B3

10

( )

B3

14

] [

M0:2.1

1

( )

B3

10

1

2

[OSR]

B11

0

COP

COPY FILE
Source

#M1:4.3

Dest

#N10:0

Length

6

] [

S:4

7

S:4/7 causes the
#M1:4.3 file to update
the #N10:0 file every
2.56 seconds.

Advertising