Configuration and Programming 4-25

M0:e.0 Bits 0 through 7 - Output Source Select (Dynamic)

Bits 0, 1, 2, and 3 represent the Physical Outputs. Bits 4, 5, 6, and 7
represent the Soft Outputs.

The status of these bits determines whether an output is controlled by
the module (when the Function Control bit is set to 1), or by the user
program.

A logic 0 in any of these positions means that the corresponding
output is under module control. A logic 1 means that the
corresponding output is under user program control (refer to O:e.0
Direct Outputs (Dynamic)
on page 4-36.

The Output Source Select bit values are dynamic and can be changed
by the user program at any time.

M0:e.0 Bits 8 through 15

Bits 8 through 15 are reserved and must be reset to 0.

M0:e.1 Setup and Control Word

Output Source Select (bits 4-7)

Output Status

0

output is under module control

1

output is under user program control

M0:e.1

Sequencer Reset

0

0 = No Change
1 = Sequencer Reset

10 = Sequencer

0 = Linear
1 = Ring

0 = Disable Counter
1 = Enable Counter

R

0 = Increment
1 = Decrement

Setup and Control Word, Word 1

Enable Outputs

Counter Hold

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Soft Reset

Reset Mode

Up/Down Count Direction

Input T

ype

Function Control

Counter T

ype

Operating Mode

000 = No reset
001 = Z
010 = LS
011 = LS and Z
100 = SR
101 = SR and Z
110 = SR and LS
111 = SR, LS, and Z

0 = False
1 = True

1 = Hold

0 = Outputs OFF
1 = Outputs enabled

R

R

= Reserved, must be reset to 0

000 = Invalid
001 = Invalid
010 = Pulse & Direction/External Control
011 = Pulse & Direction/Internal Control
100 = Quadrature Encoder x1
101 = Quadrature Encoder x2
110 = Quadrature Encoder x4
111 = Up / Down Pulse Inputs