3-10 Installation and Wiring

Wiring the Removable
Terminal Block

The terminal screws can be turned with flat or cross slot screwdrivers.
Each screw should be turned tight enough to immobilize the wire’s
end. Over tightening can strip the terminal screw. The torque applied
to each screw should not exceed 5.3 inch pounds. A wiring template
for the terminal block is provided below.

Encoder Selection

Differential encoders provide the best immunity to electrical noise. We
recommend, whenever possible, to use differential encoders.

The wiring diagrams on the following pages are provided to support
the Allen-Bradley encoders you may already have.

VDC

OUT 0

OUT 1

OUT 2

OUT 3

A+

A–

Not used

Z+

Z–

LS COM

DC COM

B+

B–

Not used

LS(24VDC)

LS(12VDC)

LS(5VDC)