Publication 1746-UM006B-EN-P - August 2005

4-16 Configuration and Programming

I:e.0 Status Word

I:e.0 Bits 0 and 1

Bits 0 and 1 are reserved and must be reset to 0.

I:e.0 Bit 2 - Zero Rate Period Count

The module sets this bit to 1 whenever the Rate Period Count is found
to be zero over a Rate Period.

The bit is cleared to 0:

any time a non-zero count is obtained

when there is a Rate Period Count overflow

upon the 0 to 1 transition of the Function Control bit

This bit is updated after every Rate Period.

0 = No configuration error
1 = Invalid configuration data

0 = No overflow
1 = Overflow

0 = Invalid Rate
1 = Rate Valid

0 = No overflow
1 = Overflow

0 = No errors detected
1 = Error detected

0 = No error detected
1 = Overflow/Underflow

00 = Stopped
01 = Running
10 = Undefined
11 = Hold

0 = False Reset Mode
1 = True Reset Mode

Status Word, Word 0

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

I:e.0

Rate Valid

Rate Counter Overflow

Rate Measurement Overflow

Critical Error

Configuration Error

Pulse Counter State

Overflow/Underflow

Reset Input

R

R

R

R

R

R

0 = Nonzero Rate Period count
1 = Rate Period Count is 0

Zero Rate Period Count

R

= Reserved, must be reset to 0

Zero Rate Period Count (bit 2) Cause

0

Non-zero count is obtained, rate period overflow, or,
counter function has been enabled

1

Rate Period Count is Zero over a Rate Period