3-4 Installation and Wiring

JW1 Settings

Select 300 µs or 10 ms filtering to debounce the limit switch input.
Position the jumper as follows:

The LS input allows you to make a direct connection to nominal
voltage levels of 5, 12, or 24V dc. The ON voltage ranges are as
follows:

The figure below indicates how to connect a limit switch and 12V dc
supply to the module. Jumper JW1 is placed for a 10 ms debounce.

This input is intended for connection to a limit switch used to reset
the counter. The LS input can be used alone as a reset or in
combination with the Z input, or Soft Reset (refer to M0:e.1/5-7).

Wiring terminal

Limit Switch ON range

LS (24V dc)

16.5-30V dc

LS (12V dc)

9.4- 10.5V dc

LS (5V dc)

3.8-5.5V dc

JW1

3 2 1

JW1

3 2 1

10 ms Filter

300 us Filter

HSCE module

+

12V dc

Limit switch

LS (24V dc)

LS (12V dc)

LS (5V dc)

LS COM

JW1

3 2 1

wiring terminals

jumper placed for 10 ms filtering

ATTENTION

Only connect one LS input range at a time.
Otherwise, the module will be damaged.