Module Operation 2-15

Range Outputs - Range and Rate Mode

Output Source Select

The Output Source Select (M0:e.0/0-7) is used to specify whether the
outputs are activated by the user program or from the module. Each
bit represents an output. When set to 1, the associated output is
controlled by the user program. When an Output Source Select bit is
set to 1, the user program can set a bit in the Direct Output field
(O:e.0/0-7) which turns an output ON.

Output Source Select - bits 0 to 7

Range 2 and 1 Outputs, Word 3

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

M0:e.3

Range 4 and 3 Outputs, Word 4

M0:e.4

Range 6 and 5 Outputs, Word 5

M0:e.5

Range 8 and 7 Outputs, Word 6

M0:e.6

Range 10 and 9 Outputs, Word 7

M0:e.7

Range 12 and 11 Outputs, Word 8

M0:e.8

Physical Output patterns

Soft Output patterns

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Preset 2 and 1 Outputs, Word 4

M0:e.4

M0:e.15

Physical Output patterns

Preset 24 and 23 Outputs, Word 15

Soft Output patterns

Step Outputs - Sequencer
Mode

Output Source Select, Word 0

Bit Number (decimal)

Output Source Select bits

for Soft Outputs

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

M0:e.0

Output Source Select bits

for Physical Outputs

Advertising