6-2 Application Examples

The following is a brief description of the application.

The processor monitors the number of pulses that the module
has counted. If this number is greater than or equal to 2500, bit
B3/0 is energized. If this number is less than 2500, bit B3/1 is
energized.

If the count reaches 30,000 the accumulator of the module resets
to zero automatically.

If you press the Reset Push Button, the accumulator of the
module is reset, regardless of the current count. (Pressing the
Reset Push Button causes the module’s soft reset bit to latch and
remain latched until the module acknowledges the reset by
setting the Input Reset bit.)

Configuration Worksheets

Shown below is the Range/Rate Mode Configuration Worksheet for
M0 Files. A blank worksheet is supplied in Appendix D. For the
Count-Only example, place the M0 configuration for the module in
data N10.

Direct Outputs (page 4-15)

Output Source Select (page 4-3)