Installation and Wiring 3-7

Input and Output
Connections

Input and output wiring terminals are located on the front of the
module, behind the terminal cover. When you connect input and
output devices, you will also be concerned with the settings of dip
switch SW1 (input connections), dip switch SW2 (output
connections), and jumper JW1 (limit switch input connections). Refer
to Dip Switch and Jumper Locations beginning on page 3-2 for the
location and description of SW1, SW2, and JW1.

VDC

OUT 1

OUT 3

A+

A–

Z+

Z–

LS COM

OUT 0

OUT 2

DC COM

B+

B–

Not used

Not used

LS(24VDC)

LS(12VDC)

LS(5VDC)

FAULT

1

2

3

4

5

6

7

0

A

B

Z

LS

VDC

OUT 0

OUT 1

OUT 2

OUT 3

A+

A–

Not used

Z+

Z–

LS COM

DC COM

B+

B–

Not used

LS (24 VDC)

LS (12 VDC)

LS (5 VDC)

OUTPUT

INPUT

HSCE

Discrete Output Wiring

VDC must be externally supplied by the user.
See page 3-8 for output wiring.

Limit Switch and Encoder Input Wiring

See pages 3-11 through 3-15 for input wiring.

ATTENTION

Do not use incandescent lamps as output indicators.
The high peak inrush current required to heat the
filament can damage the module’s output circuits.
Use LED type indicators that satisfy the output circuit
ratings, such as Allen-Bradley 800A and 800T LED
indicators.