Quadrature encoder input, Quadrature encoder input -5 – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 23

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

Module Operation 2-5

Quadrature Encoder Input

The figure below shows a quadrature encoder connected to inputs A,
B, and Z. The count direction is determined by the phase angle
between input A and input B. If A leads B, the counter increments. If
B leads A, the counter decrements.

The counter resolution can be selected so that the count increments/
decrements on one edge of input A only (X1), on both edges of input
A (X2), or on both edges of input A and input B (X4).

The counter can be reset using the Z input, as described in Counter
Reset Control o
n page 2-9.

IMPORTANT

The connection of A, B, and Z is critical, refer to
Chapter 3 and Appendix C.

A

B

Z

(Reset input)

Quadrature encoder

module

12

11

10

9

8

7

6

5

4

3

2

1

2

3

4

5

6

7

8

9

10

1

6

5

4

3

2

1

1

2

3

4

5

1

2

3

2

1

Forward rotation

Reverse rotation

A

B

X1

count

X2

count

X4

count

11

Input A

Input B

Input Z

Advertising