Installation and Wiring 3-5

Installing the Module

Installation procedures for this module are the same as any other
discrete I/O or specialty module.

1. Align the full sized circuit board with the rack card guide. The

first slot (slot 0) of the first rack is reserved for the CPU.

2. Slide the module into the rack until the top and bottom latches

are latched. To remove the module, press the releases at the top
and bottom of the module and slide it out.

3. Make sure the removable terminal wiring block is attached to

the module and all wires are connected to the terminal block.
Refer to page 3-10 for more information regarding wiring the
terminal block.

4. Insert the cable tie in the slots and secure the cable.

5. Cover all unused slots with the Card Slot Filler, Catalog Number

1746-N2.

IMPORTANT

Set the dip switches before installing the module.

ATTENTION

Disconnect power before attempting to install,
remove, or wire the module.

Make sure your SLC power supply has adequate
reserve current capacity. The module requires
320 mA at 5 volts.