I:e.5 reserved, I:e.5 reserved -22 – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 82

Advertising
background image

Publication 1746-UM006B-EN-P - August 2005

4-22 Configuration and Programming

I:e.4 Bits 0 through 7 - Configuration Error Code

I:e.4 Bits 8 through 15 - Output Status

These bits reflect the current state of both the Soft and Physical
Outputs. If the Enable Output bit (M0:e.1/1) is false or if the processor
is not in run mode, the Physical Outputs are not active.

Bits 8-11 represent the Physical Outputs 0-3. Bits 12-15 represent the
Soft Outputs 4-7.

I:e.5 Reserved

Configuration
Error Code

Reason

Critical
Error

Action

Hex Binary

01

0000 0001 not defined

-

reconfigure

(1)

(1) The Function Control bit must be reset to 0, the parameter must be changed, and the Function Control bit is

then set to 1

.

02

0000 0010 max count = 0 (ring)

yes

reconfigure

(1)

03

0000 0011 invalid operating mode

yes

reconfigure

(1)

04

0000 0100 invalid input type

yes

reconfigure

(1)

05

0000 0101 static parameter changed

yes

reconfigure

(1)

06

0000 0110 ranges active = 0

no

change parameter

07

0000 0111 rate period = 0

no

change parameter

08

0000 1000 linear counter reset value out of range

no

change parameter

09

0000 1001 sequencer preset > max. count

no

change parameter