Configuration and Programming 4-3

M0:e.0 Output Source Select

M0:e.0 Bits 0 through 7 - Output Source Select (Dynamic)

Bits 0, 1, 2, and 3 represent the Physical Outputs. Bits 4, 5, 6, and 7
represent the Soft Outputs.

The status of these bits determines whether an output is controlled by
the module (when the Function Control bit is set to 1), or by the user
program.

A logic 0 in any of these positions means that the corresponding
output is under module control. A logic 1 means that the
corresponding output is under user program control (refer to 0:e.0/0-7
Direct Outputs
).

The Output Source Select bit values are dynamic and can be changed
by the user program at any time.

M0:e.0 Bits 8 through 15

Bits 8 through 15 are reserved and must be reset to 0.

Output Source Select (bits 4-7)

Output Status

0

Output is under module control

1

Output is under user program control

M0 Word 0

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

M0:e.0

Output Source Select

Soft Outputs

Output Source Select

Physical Outputs

R R R R R R R R