Chapter 4 - configuration and programming, Configuration worksheets, Dynamic and static parameters – Rockwell Automation 1746-HSCE,D17466.5 High-Speed Counter Module User Manual

Page 61: Chapter 4, Configuration and programming, Chapter

Advertising
background image

1

Publication 1746-UM006B-EN-P - August 2005

Chapter

4

Configuration and Programming

This chapter contains the Output, Input and M0 file information.

a discussion of Dynamic and Static Parameters

M0 file contents for range and rate modes

output data file contents for range and rate mode operation

input data file contents for range and rate mode operation

M0 file contents for sequencer mode operation

output data file contents for sequencer mode operation

input data file contents for sequencer mode operation

Configuration Worksheets

To assist you in the configuration of your SLC processor and the
monitoring of your module, configuration worksheets are contained in
appendixes D and E. Appendix D contains worksheets for Range and
Rate Mode operation. Appendix E contains worksheets for Sequencer
operation. Do not remove the worksheets from the manual,
photocopy them so they can be re-used.

The worksheets are used in Chapter 6, Application Examples. In
addition, the Configuration Data Tables are shown for comparison to
the worksheets.

Dynamic and Static
Parameters

This chapter identifies parameters as Dynamic and Static. Dynamic
Parameters immediately update the operating conditions. They do not
disrupt counter operation. Only one Dynamic Parameter should be
changed at a time.

Static Parameters can only be changed when the Function Control bit
is reset to 0. They will not alter operating conditions until the Function
Control Bit is set to 1. A module fault occurs when you try to change a
static parameter while the Function Control bit is set to 1.