Publication 1746-UM006B-EN-P - August 2005

E-4 Sequencer Mode Configuration Worksheets

Reset Value/Maximum Count Value (page 4-35)

Input Data File Worksheets

Shown below is the Sequencer Mode Configuration Worksheet for the
Input Data file.

Status Word (page 4-37)

Accumulated Count, Rate Period Count, and Rate Measurement (decimal)
(page 4-42)

ATTENTION

The module will fault on power-up if you do not
enter a value.

M0:e.41

Reset Value/Maximum Count Value

Ring counter – Maximum Count Value range is 1 to 32767 (rollover at +32767)
Linear counter – Reset Value range is –32767 to +32767.

Status Word

I:e.0

Bit Number (decimal)

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

R

R

R

R

R

0 = No overflow
1 = Overflow

0 = Invalid rate
1 = Rate valid

00 = Stopped
01 = Running
10 = Undefined
11 = Hold

0 = False Reset Mode
1 = True Reset Mode

1 = End of Sequence

0 = No configuration error
1 = Invalid configuration data

0 = No overflow
1 = Overflow

0 = No error detected
1 = Overflow/Underflow

0 = No error detected
1 = Error detected

0 = Nonzero Rate Period count
1 = Rate Period Count is 0

R

= Reserved, must be reset to 0

Overflow/Underflow (page 4-41)

Configuration Error (page 4-41) Rate Counter Overflow (page 4-39) Zero Rate Period Count (page 4-38)

Pulse Counter State (page 4-42) Reset Input (page 4-41)

Critical Error (page 4-40)

Rate Measurement Overflow (page 4-39)

Rate Valid (page 4-38)

Sequence Done (page 4-40)

I:e.1

I:e.2

I:e.3

Accumulated Count

Rate Period Count

Rate Measurement (Hz)